RO HVAC Duct Sizer

Professional HVAC duct sizing calculator

Design Inputs

Calculated Duct

Round duct—
Rectangular duct—
Air velocity—FPM
Friction rate—in. w.c. / 100 ft

Airflow & Velocity Calculator

Velocity = CFM ÷ duct area. Required area = CFM ÷ target velocity.

Pressure Drop / Friction Helper

Design friction rate = available static pressure × 100 ÷ total effective length.

Round ↔ Rectangular Size Converter

Equivalent diameter: De = 1.30 × (W×H)^0.625 ÷ (W+H)^0.25.

Common Design Ranges

ApplicationTypical velocitySuggested max
Residential supply700–900 FPM900 FPM
Supply branch500–800 FPM800 FPM
Return400–700 FPM700 FPM
Light commercial900–1500 FPM1500 FPM

Standard Round Sizes

4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36 in

Design Notes

  • Use room-by-room design airflow rather than floor-area rules of thumb.
  • Keep rectangular aspect ratio preferably at or below 4:1.
  • Flex duct generally needs additional allowance for installed roughness and compression.
  • Verify final design against applicable ASHRAE, ACCA, SMACNA and local requirements.